MONITORING
4–258
Path:
Setpoints > Monitoring > Transformer > Tap Changer Failure
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 5.00 s
BLOCK
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
OUTPUT RELAYS
Range: Do Not Operate, Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS