GE 845 Instruction Manual page 22

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

SPECIFICATIONS
1–14
PHASE UNDERVOLTAGE (27P)
Voltage: ................................................................... Fundamental Phasor Magnitude
Minimum Voltage: .............................................. 0.00 to 1.50 x VT in steps of 0.01 x VT
Pickup Level: ......................................................... 0.00 to 1.50 x VT in steps of 0.01 x VT
Dropout Level:...................................................... 102 to 103% of Pickup
Level Accuracy:.................................................... ±0.5% of reading from 10 to 208 V
Phases Required for Operation:................... Any one, Any two, All three
Undervoltage Curves:....................................... Definite Time or Inverse Time
Pickup Time Delay:............................................. 0.000 to 6000.000 s in steps of 0.001s
Operate Time: ...................................................... < 20 ms at 0.90 x pickup at 60 Hz
Curve Timing Accuracy: .................................. at < 0.90 x pickup: ± 3.5% of curve delay or ± ½ cycle
AUXILIARY UNDERVOLTAGE (27X)
Operating Parameter: ...................................... Vx (Phasor)
Minimum Voltage: .............................................. 0.00 to 1.50 x VT in steps of 0.01 x VT
Pickup Level: ......................................................... 0.00 to 1.50 x VT in steps of 0.01 x VT
Dropout Level:...................................................... 102 to 103% of Pickup
Level Accuracy:.................................................... ± 0.5% of reading from 10 to 208 V
Undervoltage Curves:....................................... Definite Time or GE IAV Inverse Time
Pickup Time Delay:............................................. 0.000 to 6000.000 s in steps of 0.001 s
Operate Time: ...................................................... < 20 ms at 0.90 x pickup at 60 Hz
Curve Timing Accuracy: .................................. at < 0.90 x pickup: ± 3.5% of curve delay or ± ½ cycle
PHASE OVERVOLTAGE (59P)
Votage: .................................................................... Fundamental Phasor Magnitude
Pickup Level: ......................................................... 0.02 to 3.00 x VT in steps of 0.01 x VT
Dropout Level:...................................................... 97 to 98% of Pickup
Level Accuracy:.................................................... ±0.5% of reading from 10 to 208 V
Phases Required for Operation:................... Any one, Any two, All three
Pickup Time Delay:............................................. 0.000 to 6000.000 s in steps of 0.001s (Definite Time)
Dropout Time Delay: ......................................... 0.000 to 6000.000 s in steps of 0.001s (Definite Time)
Pickup Accuracy:................................................. Per phase voltage input channel error
Operate Time: ...................................................... < 25 ms at 1.1 x pickup at 60Hz
Timer Accuracy: .................................................. ± 3% of delay setting or ± ¼ cycle (whichever is greater) from
AUXILIARY OVERVOLTAGE (59X)
Operating Parameter: ...................................... V
Pickup Level: ......................................................... 0.00 to 3.00 x VT in steps of 0.01 x VT
Dropout Level:...................................................... 97 to 98% of Pickup
Level Accuracy:.................................................... ±0.5% of reading from 10 to 208 V
Pickup Time Delay:............................................. 0.000 to 6000.000 s in steps of 0.001s
Dropout Time Delay: ......................................... 0.000 to 6000.000 s in steps of 0.001s
Operate Time: ...................................................... < 25 ms at 1.1 x pickup at 60Hz
Timer Accuracy: .................................................. ± 3% of delay setting time or ± ¼ cycle (whichever is greater)
< 25 ms at 0.90 x pickup at 50 Hz
(whichever is greater) from pickup to operate
< 25 ms at 0.90 x pickup at 50 Hz
(whichever is greater) from pickup to operate
< 30 ms at 1.1 x pickup at 50Hz
pickup to operate
X
< 30 ms at 1.1 x pickup at 50Hz
from pickup to operate
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents