4.4 USING 750/760 PC
2. After configuring the setpoints (see Section 4.4.3: ENTERING SETPOINTS on page 4–8) select the File >
Save As menu item. If the 750/760 PC Program is communicating with a relay, selecting Save As will save
the setpoints of the connected relay to a file.
3. The following dialog box will pop-up. Enter the file name under which the file will be saved in the File Name
box or click on any of the file names displayed in the box below. All 750 setpoint files should have the
extension . 750. All 760 setpoint files should have the extension . 760. Click on OK to proceed:
4
4. The program will then read all the relay setpoint values and store them to the selected file.
The following steps show how to download a setpoint file to a relay:
1. From the File menu select Open.
2. The following dialog box will pop-up. The program will display all filenames with the extension * . 750 for 750
file type and *.760 for 760 file type. Select the file name of the setpoint file to download to the 750/760 – the
selected file name will appear in the file name box. Click the OK button to continue.
3. From the File menu select Properties. Change the file properties, if necessary, to be consistent with the
relay that this setpoint file is going to be loaded into.
4. From the File menu select Send Info to Relay. The program will then prompt you to confirm or abort the
process - click on Yes to download the setpoints to the relay or No to abort.
4-
10
Courtesy of NationalSwitchgear.com
Figure 4–10: SAVE AS DIALOG BOX
Figure 4–11: OPEN FILE DIALOG BOX