GE 845 Instruction Manual page 365

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

CHAPTER 4: SETPOINTS
FASTPATH:
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 4-108: Trip Coil Circuit with Monitoring
Figure 4-109: Close Coil Circuit with Monitoring
To monitor the trip coil circuit integrity, use the relay terminals "FA_1 NO" and "FA_1 COM"
to connect the Trip coil, and provide a jumper between terminals "FA_1 COM" and "FA_1
OPT/V" voltage monitor).
Some applications require monitoring the Trip coil or/and Close coil continuously,
regardless of the breaker position (open or closed). This can be achieved by connecting a
suitable resistor (see the table Value of Resistor "R") across the breaker auxiliary contact(s)
52a in the trip circuit (across 52b contact(s) for Close coil). With such connections, the
trickle current is maintained by the resistor. For these applications the setting for the
Bypass Breaker Status should be set to ENABLED.
Output Relay 1 (TRIP)
FA_1
COM
FA_1
NO
V
FA_1
OPT/V
Output Relay 2 (CLOSE)
FA_2
COM
FA_2
NO
V
FA_2
OPT/V
MONITORING
DC +
External
Jumper
52a
contact
Trip
Coil
DC -
DC +
External
Jumper
52b
contact
Close
Coil
DC -
4–261

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents