Testing & Certification - GE 845 Instruction Manual

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

CHAPTER 1: INTRODUCTION
Testing & Certification
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
APPROVALS
Applicable Council Directive
CE compliance
Low voltage directive
EMC Directive
R&TTE Directive
North America
cULus
ISO
Manufactured under a registered
quality program
TESTING AND CERTIFICATION
Test
Dielectric voltage withstand
Impulse voltage withstand
Insulation resistance
Damped Oscillatory
Electrostatic Discharge
RF immunity
Fast Transient Disturbance
Surge Immunity
Conducted RF Immunity
Harmonics and Interharmonics
Power Frequency Immunity
Voltage interruption and Ripple
DC
Radiated & Conducted Emissions CISPR11 /CISPR22/ IEC60255-25
Sinusoidal Vibration
Shock & Bump
Seismic
Power magnetic Immunity
Pulse Magnetic Immunity
Damped Magnetic Immunity
Voltage Dip & interruption
Harmonic Immunity
Conducted RF Immunity 0-150kHz IEC61000-4-16
Ingress Protection
Environmental (Cold)
Environmental (Dry heat)
Relative Humidity Cyclic
EFT
According to
EN60255-5 / EN60255-27
EN60255-26
EN61000-6-2 / EN61000-6-4
ETSI EN300 328 ETSI EN301 489-1 ETSI
EN301-489-17
UL508
C22.2.No 14
ISO9001
Reference Standard
EN60255-5/IEC60255-27
EN60255-5/IEC60255-27
IEC60255-5/IEC60255-27
IEC60255-22-1
EN61000-4-2/IEC60255-22-2
EN61000-4-3/IEC60255-22-3
EN61000-4-4/IEC60255-22-4
EN61000-4-5/IEC60255-22-5
EN61000-4-6/IEC60255-22-6
IEC61000-4-13
IEC60255-22-7
IEC60255-11
IEC60255-21-1
IEC60255-21-2
IEC60255-21-3
IEC61000-4-8
IEC61000-4-9
IEC61000-4-10
IEC61000-4-11
IEC61000-4-13
IEC60529
IEC60068-2-1
IEC60068-2-2
IEC60068-2-30
IEEE/ANSI C37.90.1
SPECIFICATIONS
Test Level
2.3 kV
5 kV
500 VDC (test level)
2.5 kV CM, 1 kV DM,
100 kHz, 1 MHz
Level 4
Level 3
Class A and B
Level 3
Level 3
Class 3
Class A & B
PQT levels based on
IEC61000-4-29,
IEC61000-4-11 and
IEC61000-4-17
Class A
Class 1
Class 1
Class 2
Level 5
Level 4
Level 4
0, 40, 70, 80% dips, 250/
300 cycle interrupts
Class 3
Level 4
IP54 front
-40C 16 hrs
85C 16hrs
6 day humidity variant 2
4kV, 5 kHz
1–25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents