CHAPTER 4: SETPOINTS

Fault Reports

845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 4-35: Data Logger Storage Capacity
When enabled, this function monitors the pre-fault trigger. The pre-fault data are stored in
the memory for prospective creation of the fault report on the rising edge of the pre-fault
trigger. The element waits for the fault trigger as long as the pre-fault trigger is asserted,
but not shorter than 1 second. When the fault trigger occurs, the fault data is stored and
the complete report is created. If the fault trigger does not occur within 1 second after the
pre-fault trigger drops out, the element resets and no record is created.
The user programmable fault report header contains the following information:
Fault report number
Relay model
Device name
Firmware revision
Date and time of trigger
Name of pre-fault trigger (FlexLogic operand)
Name of Fault trigger (FlexLogic operand)
Active setting group at the time of pre-fault trigger
Active setting group at the time of fault trigger.
The fault report continuous with the following information:
All current and voltage phasors (one cycle after the fault trigger)
DEVICE
4–69