When enabled, the SQO instruction increments the position, moves the data at
the position through the Mask, and stores the result in the Destination. If .POS >
.LEN, the instruction wraps around to the beginning of the sequencer array and
continues with .POS = 1.
Typically, use the same CONTROL structure as the SQI and SQL instructions.
The SQO instruction operates on contiguous memory.

Enter an Immediate Mask Value

When you enter a mask, the programming software defaults to decimal values. If
you want to enter a mask by using another format, precede the value with the
correct prefix.
Prefix
16#
8#
2#
Not affected
None
Sequencer Instructions (SQI, SQO, SQL)
Description
Hexadecimal
For example; 16#0F0F
Octal
For example; 8#16
Binary
For example; 2#00110011
Chapter 10
441