Attribute
Data Type
DeviceName
SINT[33]
ProductCode
INT
ProductRev
INT
SerialNumber
DINT
Status
INT
Type
INT
Vendor
INT

ControllerDevice Attributes

The ControllerDevice object identifies the physical hardware of the controller.
Instruction
Description
GSV
ASCII string that identifies the catalog number of the controller and memory board. The first byte
contains a count of the number of ASCII characters returned in the array string.
GSV
Identifies the type of controller:
Value
Meaning
15
SoftLogix5800
49
PowerFlex with DriveLogix5725
52
PowerFlex with DriveLogix5730
53
Emulator
54
1756-L61 ControlLogix
55
1756-L62 ControlLogix
56
1756-L63 ControlLogix
57
1756-L64 ControlLogix
64
1769-L31 CompactLogix
65
1769-L35E CompactLogix
67
1756-L61S GuardLogix
68
1756-L62S GuardLogix
69
1756-LSP GuardLogix
72
1768-L43 CompactLogix
74
1768-L45 CompactLogix
76
1769-L32C CompactLogix
77
1769-L32E CompactLogix
80
1769-L35CR CompactLogix
85
1756-L65 ControlLogix
86
1756-L63S GuardLogix
87
1769-L23E-QB1 CompactLogix
88
1769-L23-QBFC1 CompactLogix
89
1769-L23E-QBFC1 CompactLogix
GSV
Identifies the current product revision. Display should be hexadecimal. The low byte contains the
major revision; the high byte contains the minor revision.
GSV
Serial number of the device. The serial number is assigned when the device is built.
GSV
Device Status BitsController Status Bits
7...4
Meaning13...12Meaning
0000
Reserved01Keyswitch in run
0001
Flash update in progress10Keyswitch in program
0010
Reserved11Keyswitch in remote
0011
Reserved
0100
Flash is bad15...14Meaning
0101
Faulted modes01Controller is changing modes
0110
Run10Debug mode if controller in run mode
0111
Program
Fault Status Bits
11...8
Meaning
0001
Recoverable minor fault
0010
Unrecoverable minor fault
0100
Recoverable major fault
1000
Unrecoverable major fault
GSV
Identifies the device as a controller. Controller = 14.
GSV
Identifies the vendor of the device. Allen-Bradley = 0001.
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Input/Output Instructions (MSG, GSV, SSV, IOT)
Chapter 4
201

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents