Allen-Bradley Logix5000 Reference Manual page 168

1756 controllogix, 1768 compactlogix, 1769 compactlogix, 1789 softlogix, 1794 flexlogix, powerflex 700s with drivelogix
Hide thumbs Also See for Logix5000:
Table of Contents

Advertisement

Chapter 4
Input/Output Instructions (MSG, GSV, SSV, IOT)
Extended
Description
Error Code
(Hex)
2001
Excessive IOI
2002
Bad parameter value
2018
Semaphore reject
201B
Size too small
201C
Invalid size
2100
Privilege failure
2101
Invalid keyswitch position
2102
Password invalid
2103
No password issued
2104
Address out of range
2105
Address and how many out of range
2106
Data in use
2107
Type is invalid or not supported
2108
Controller in upload or download mode
168
These are the extended error codes for error code 001F.
Extended Error Code
(Hex)
0203
These are the extended error codes for error code 0004 and 0005.
Extended Error Code
(Hex)
0000
0001
These are the extended error codes for error code 00FF.
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Description
Connection timeout
Description
extended status out of memory
extended status out of instances
Extended
Description
Error Code
(Hex)
2109
Attempt to change number of array dimensions
210A
Invalid symbol name
210B
Symbol does not exist
210E
Search failed
210F
Task cannot start
2110
Unable to write
2111
Unable to read
2112
Shared routine not editable
2113
Controller in faulted mode
2114
Run mode inhibited