Allen-Bradley Logix5000 Reference Manual page 170

1756 controllogix, 1768 compactlogix, 1769 compactlogix, 1789 softlogix, 1794 flexlogix, powerflex 700s with drivelogix
Hide thumbs Also See for Logix5000:
Table of Contents

Advertisement

Chapter 4
Input/Output Instructions (MSG, GSV, SSV, IOT)
Table 2 - PLC and SLC Error Codes (hex) (Continued)
R9.x And Earlier
.ERR
.EXERR
00F0
000D
00F0
000E
00F0
000F
00F0
0010
00F0
0011
00F0
0012
00F0
0013
00F0
0014
00F0
0015
00F0
0016
00F0
0017
00F0
0018
00F0
0019
00F0
001A
00F0
001B
00F0
001C
00F0
001D
170
R10.x And Later
.ERR
.EXERR
F00D
F00E
F00F
F010
F011
F012
F013
F014
F015
F016
F017
F018
F019
F01A
F01B
F01C
F01D
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Description
Request is redundant
Command cannot be executed
Overflow; histogram overflow
No access
Data type requested does not match data available
Incorrect command parameters
Address reference exists to deleted area
Command execution failure for unknown reason
PLC-3 histogram overflow
Data conversion error
The scanner is not available to communicate with a 1771 rack adapter
The adapter is no available to communicate with the module
The 1771 module response was not valid
Duplicate label
File owner active - the file is being used
Program owner active - someone is downloading or editing online
Disk file is write protected or otherwise not accessible (offline only)
Disk file is being used by another application
Update not performed (offline only)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents