To Auto - Allen-Bradley Logix5000 Reference Manual

1756 controllogix, 1768 compactlogix, 1769 compactlogix, 1789 softlogix, 1794 flexlogix, powerflex 700s with drivelogix
Hide thumbs Also See for Logix5000:
Table of Contents

Advertisement

Chapter 13
Special Instructions (FBC, DDT, DTR, PID)
Manual Mode of Control
Software manual (.SWM)
Manual (.MO)
520
Where:
Variable
Description
K
Proportional gain (unitless)
P
K
p
K
Integral gain (seconds
i
To convert between K
K
Derivative gain (seconds)
d
To convert between K
K
d
K
Controller gain (unitless)
C
T
Reset time (minutes/repeat)
i
T
Rate time (minutes)
d
SP
Setpoint
PV
Process variable
E
Error [(SP-PV) or (PV-SP)]
BIAS
Feedforward or bias
CV
Control variable
dt
Loop update time
If you do not want to use a particular term of the PID equation, just set its gain
to zero. For example if you want no derivative action, set K
Anti-reset Windup and Bumpless Transfer from Manual to Auto
The PID instruction automatically avoids reset windup by preventing the
integral term from accumulating whenever the CV output reaches its
maximum or minimum values, as set by .MAXO and .MINO. The
accumulated integral term remains frozen until the CV output drops below its
maximum limit or rises above its minimum limit. Then normal integral
accumulation automatically resumes.
The PID instruction supports two manual modes of control.
Description
Also known as set output mode
Lets the user set the output % from the software
The set output (.SO) value is used as the output of the loop. The set output value typically comes
from an operator input from an operator interface device.
Takes the tieback value, as an input, and adjusts its internal variables to generate the same value
at the output
The tieback input to the PID instruction is scaled to 0-100% according to the values of .MINTIE
and .MAXTIE and is used as the output of the loop. The tieback input typically comes from the
output of a hardware hand/auto station that is bypassing the output from the controller.
Important: Manual mode overrides software manual mode if both mode bits are set on.
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
= K
unitless
c
-1
)
(integral gain) and T
i
K
C
---------- -
K
=
i
60T
i
(derivative gain) and T
d
= K
(T
) 60
c
d
(reset time), use:
i
(rate time), use:
d
or T
equal to zero.
d
d

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents