Chapter 1
FactoryTalk Alarms and Events Logix-based Instructions (ALMD, ALMA)
84
· Typically 2.2 KB per analog alarm with no associated tags
Analog Alarm Example
Analog alarm with no associated tags and this configuration:
· HH Alarm message: Level Alarm
· H Alarm Message: Level Alarm
· L Alarm Message: Level Alarm
· LL Alarm Message: Level Alarm
· Rate of Change Positive Message: Fill Too Fast
· Rate of Change Negative Message: Empty Too Fast
· Alarm Class: Tank Farm A
Analog alarm with two associated tags and this configuration:
· HH Alarm message: Level Alarm
· H Alarm Message: Level Alarm
· L Alarm Message: Level Alarm
· LL Alarm Message: Level Alarm
· Rate of Change Positive Message: Fill Too Fast
· Rate of Change Negative Message: Empty Too Fast
· Alarm Class: Tank Farm A
· Associated Tag 1 = DINT data type
· Associated Tag 2 = DINT data type
Analog alarm with two associated tags and this configuration:
· HH Alarm message: Level Alarm
· H Alarm Message: Level Alarm
· L Alarm Message: Level Alarm
· LL Alarm Message: Level Alarm
· Rate of Change Positive Message: Fill Too Fast
· Rate of Change Negative Message: Empty Too Fast
· Alarm Class: Tank Farm A
· Associated Tag 1 = DINT data type
· Associated Tag 2 = STRING data type
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Approximate Size
2228 bytes
2604 bytes
4536 bytes