Error Code (Hex)
Description
00D0
The scanner did not receive a block-transfer response from the block-transfer module within 3.5
seconds of the request
00D1
The checksum from the read response did not match the checksum of the data stream
00D2
The scanner requested either a read or write but the block-transfer module responded with the
opposite
00D3
The scanner requested a length and the block-transfer module responded with a different length
00D6
The scanner received a response from the block-transfer module indicating the write request failed
00EA
The scanner was not configured to communicate with the rack that would contain this block-transfer
module
00EB
The logical slot specified is not available for the given rack size
00EC
There is currently a block-transfer request in progress and a response is required before another
request can begin
00ED
The size of the block-transfer request is not consistent with valid block-transfer size requests
00EE
The type of block-transfer request is not consistent with the expected BT_READ or BT_WRITE
00EF
The scanner was unable to find an available slot in the block-transfer table to accommodate the
block-transfer request
00F0
The scanner received a request to reset the remote I/O channels while there were outstanding block-
transfers
00F3
Queues for remote block-transfers are full
00F5
No communication channels are configured for the requested rack or slot
00F6
No communication channels are configured for remote I/O
00F7
The block-transfer timeout, set in the instruction, timed out before completion
00F8
Error in block-transfer protocol - unsolicited block-transfer
00F9
Block-transfer data was lost due to a bad communication channel
00FA
The block-transfer module requested a different length than the associated block-transfer instruction
00FB
The checksum of the block-transfer read data was wrong
00FC
There was an invalid transfer of block-transfer write data between the adapter and the block-transfer
module
00FD
The size of the block-transfer plus the size of the index in the block-transfer data table was greater
than the size of the block-transfer data table file

Block-Transfer Error Codes

These are the Logix5000 block-transfer specific error codes.
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Input/Output Instructions (MSG, GSV, SSV, IOT)
Chapter 4
Display In Software
Unknown error