Chapter 1
FactoryTalk Alarms and Events Logix-based Instructions (ALMD, ALMA)
Input Parameter
Data Type
ROCPosProgAck
BOOL
ROCPosOperAck
BOOL
ROCNegProgAck
BOOL
ROCNegOperAck
BOOL
ProgSuppress
BOOL
OperSuppress
BOOL
ProgUnsuppress
BOOL
OperUnsuppress
BOOL
ProgDisable
BOOL
OperDisable
BOOL
ProgEnable
BOOL
OperEnable
BOOL
AlarmCountReset
BOOL
HHLimit
REAL
58
Description
Positive rate of change program acknowledge. Set by the user program to acknowledge a positive rate-of-
change condition. Requires a cleared-to-set transition while the alarm condition is unacknowledged.
Default is cleared.
Positive rate of change operator acknowledge. Set by the operator interface to acknowledge a positive
rate-of-change condition. Requires a cleared-to-set transition while the alarm condition is
unacknowledged. The alarm instruction clears this parameter.
Default is cleared.
Negative rate of change program acknowledge. Set by the user program to acknowledge a negative rate-
of-change condition. Requires a cleared-to-set transition while the alarm condition is unacknowledged.
Default is cleared.
Negative rate of change operator acknowledge. Set by the operator interface to acknowledge a negative
rate-of-change condition. Requires a cleared-to-set transition while the alarm condition is
unacknowledged. The alarm instruction clears this parameter.
Default is cleared.
Set by the user program to suppress the alarm.
Default is cleared.
Set by the operator interface to suppress the alarm. The alarm instruction clears this parameter.
Default is cleared.
Set by the user program to unsuppress the alarm. Takes precedence over Suppress commands.
Default is cleared.
Set by the operator interface to unsuppress the alarm. Takes precedence over Suppress commands. The
alarm instruction clears this parameter.
Default is cleared.
Set by the user program to disable the alarm.
Default is cleared.
Relay Ladder
Copied from the instruction operand.
Structured Text
Copied from the instruction operand.
Set by the operator interface to disable the alarm. The alarm instruction clears this parameter.
Default is cleared.
Set by the user program to enable the alarm. Takes precedence over a Disable command.
Default is cleared.
Relay Ladder
Copied from the instruction operand.
Structured Text
Copied from the instruction operand.
Set by the operator interface to enable the alarm. Takes precedence over Disable command. The alarm
instruction clears this parameter.
Default is cleared.
Set by the user program to reset the alarm counts for all conditions. A cleared-to-set transition resets the
alarm counts to zero.
Default is cleared.
High High alarm limit.
Valid = HLimit < HHLimit < maximum positive float.
Default = 0.0.
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011