Plc And Slc Error Codes (.Err) - Allen-Bradley Logix5000 Reference Manual

1756 controllogix, 1768 compactlogix, 1769 compactlogix, 1789 softlogix, 1794 flexlogix, powerflex 700s with drivelogix
Hide thumbs Also See for Logix5000:
Table of Contents

Advertisement

Table 2 - PLC and SLC Error Codes (hex)
R9.x And Earlier
.ERR
.EXERR
0010
0020
0030
0040
0050
0060
0070
0080
0090
00B0
00F0
0001
00F0
0002
00F0
0003
00F0
0004
00F0
0005
00F0
0006
00F0
0007
00F0
0008
00F0
0009
00F0
000A
00F0
000B
00F0
000C

PLC and SLC Error Codes (.ERR)

Logix firmware revision 10.x and later provides new error codes for errors that are
associated with PLC and SLC message types (PCCC messages).
·This change lets RSLogix 5000 software display a more meaningful
description for many of the errors. Previously the software did not give a
description for any of the errors associated with the 00F0 error code.
·The change also makes the error codes more consistent with errors
returned by other controllers, such as PLC-5 controllers.
The following table shows the change in the error codes from R9.x and earlier to
R10.x and later. As a result of the change, the .ERR member returns a
unique value for each PCCC error. The .EXERR is no longer required for
these errors.
R10.x And Later
.ERR
.EXERR
1000
2000
3000
4000
5000
6000
7000
8000
9000
B000
F001
F002
F003
F004
F005
F006
F007
F008
F009
F00A
F00B
F00C
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Input/Output Instructions (MSG, GSV, SSV, IOT)
Description
Illegal command or format from local processor
Communication module not working
Remote node is missing, disconnected, or shut down
Processor connected but faulted (hardware)
Wrong station number
Requested function is not available
Processor is in Program mode
Processor's compatibility file does not exist
Remote node cannot buffer command
Processor is downloading so it is not accessible
Processor incorrectly converted the address
Incomplete address
Incorrect address
Illegal address format - symbol not found
Illegal address format - symbol has 0 or greater than the maximum number of
characters supported by the device
Address file does not exist in target processor
Destination file is too small for the number of words requested
Cannot complete request
Situation changed during multipacket operation
Data or file is too large
Memory unavailable
Target processor cannot put requested information in packets
Privilege error; access denied
Requested function is not available