Output Parameter
Data Type
SeverityInv (Status.2)
BOOL
AlarmLimitsInv (Status.3)
BOOL
DeadbandInv (Status.4)
BOOL
ROCPosLimitInv (Status.5)
BOOL
ROCNegLimitInv (Status.6)
BOOL
ROCPeriodInv (Status.7)
BOOL
FactoryTalk Alarms and Events Logix-based Instructions (ALMD, ALMA)
Description
Alarm severity configuration is invalid.
If severity <1, the instruction uses Severity = 1.
If severity >1000, the instruction uses Severity = 1000.
Alarm Limit configuration is invalid (for example, LLimit < LLLimit). If invalid, the instruction clears all
level conditions active bits. Until the fault is cleared, no new level conditions can be detected.
Deadband configuration is invalid. If invalid, the instruction uses Deadband = 0.0.
Valid = 0 ≤ Deadband < Span from first enabled low alarm to the first enabled high alarm.
Positive rate-of-change limit invalid. If invalid, the instruction uses ROCPosLimit = 0.0, which disables
positive rate-of-change detection.
Negative rate-of-change limit invalid. If invalid, the instruction uses ROCNegLimit = 0.0, which
disables negative rate-of-change detection.
Rate-of-change period invalid. If invalid, the instruction uses ROCPeriod = 0.0, which disables rate-of-
change detection.
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011