One Shot Falling (Osf); Relay Ladder Operands - Allen-Bradley Logix5000 Reference Manual

1756 controllogix, 1768 compactlogix, 1769 compactlogix, 1789 softlogix, 1794 flexlogix, powerflex 700s with drivelogix
Hide thumbs Also See for Logix5000:
Table of Contents

Advertisement

One Shot Falling (OSF)

Description:
Arithmetic Status Flags:
Fault Conditions:
The OSF instruction sets or clears the output bit depending on the status of the
storage bit.
This instruction is available in structured text and function block as OSFI, see
page
112.
Operands:

Relay Ladder Operands

Operand
Storage bit
Output bit
When disabled and the storage bit is set, the OSF instruction sets the output bit.
When disabled and the storage bit is cleared, or when enabled, the OSF
instruction clears the output bit.
Rung-condition-
Storage
Output Bit
Not affected
None
Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Bit Instructions (XIC, XIO, OTE, OTL, OTU, ONS, OSR, OSF, OSRI, OSFI)
Type
Format
BOOL
Tag
BOOL
Tag
Instruction is
executed
Description
Internal storage bit
Stores the rung-condition-in from the last time the
instruction was executed
Bit to be set
Instruction resets
during next scan
Chapter 2
107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents