MODBUS MEMORY MAP
Address
Description
605A
Wattmetric Ground Fault 1 Curve
605B
Wattmetric Ground Fault 1 Multiplier
605C
Wattmetric Ground Fault 1 Block
605D
Wattmetric Ground Fault 1 Events
605E
Wattmetric Ground Fault 1 Reference Power
605F
Wattmetric Ground Fault x Reserved (9 items)
6068
...Repeated for Wattmetric Ground Fault 2
Negative Sequence Time Overcurrent (TOC) (Read/Write Grouped Setting) (2 Modules)
6300
Negative Sequence Time Overcurrent 1 Function
6301
Negative Sequence Time Overcurrent 1 Signal Source 0 to 5
6302
Negative Sequence Time Overcurrent 1 Pickup
6303
Negative Sequence Time Overcurrent 1 Curve
6304
Negative Sequence Time Overcurrent 1 Multiplier
6305
Negative Sequence Time Overcurrent 1 Reset
6306
Negative Sequence Time Overcurrent 1 Block
6308
Negative Sequence Time Overcurrent 1 Events
6309
Negative Sequence Time Overcurrent 1 Reserved (7
items)
6310
...Repeated for Negative Sequence Time Overcurrent
2
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 Modules)
6400
Negative Sequence Instantaneous OC 1 Function
6401
Negative Sequence Instantaneous OC 1 Signal
Source
6402
Negative Sequence Instantaneous Overcurrent 1
Pickup
6403
Negative Sequence Instantaneous Overcurrent 1
Delay
6404
Negative Sequence Instantaneous OC 1 Reset Delay 0 to 600
6405
Negative Sequence Instantaneous Overcurrent 1
Block
6407
Negative Sequence Instantaneous Overcurrent 1
Events
6408
Negative Sequence Instantaneous Overcurrent
Reserved (8 items)
6410
...Repeated for Negative Sequence Instantaneous OC
2
Negative Sequence Overvoltage (Read/Write Grouped Setting) (2 Modules)
64A0
Negative Sequence Overvoltage 1 Function
64A1
Negative Sequence Overvoltage 1 Source
64A2
Negative Sequence Overvoltage 1 Pickup
64A3
Negative Sequence Overvoltage 1 Pickup Delay
64A4
Negative Sequence Overvoltage 1 Reset Delay
64A5
Negative Sequence Overvoltage 1 Block
64A7
Negative Sequence Overvoltage 1 Events
64A8
...Repeated for Negative Sequence Overvoltage 2
Overfrequency (Read/Write Setting) (4 Modules)
88
Range
Units
0 to 5
---
0.01 to 2
s
0 to 65535
---
0 to 1
---
0.001 to 1.2
pu
0 to 1
---
0 to 1
---
---
0 to 30
pu
0 to 16
---
0 to 600
---
0 to 1
---
0 to 65535
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 5
---
0 to 30
pu
0 to 600
s
s
0 to 65535
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 5
---
0 to 1.25
pu
0 to 600
s
0 to 600
s
0 to 65535
---
0 to 1
---
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 2: MODBUS COMMUNICATION
Step
Format
Default
1
F236
0 (Definite
Time)
0.01
F001
100
1
F300
0
1
F102
0 (Disabled)
0.001
F001
500
1
F001
0
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
0.001
F001
1000
1
F103
0 (IEEE Mod
Inv)
0.01
F001
100
1
F104
0
(Instantaneou
s)
1
F300
0
1
F102
0 (Disabled)
1
F001
0
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
0.001
F001
1000
0.01
F001
0
0.01
F001
0
1
F300
0
1
F102
0 (Disabled)
1
F001
0
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
0.001
F001
300
0.01
F001
50
0.01
F001
50
1
F300
0
1
F102
0 (Disabled)