DNP DEVICE PROFILE
198
Analog input changes (object 32)
Analog deadbands (object 34)
Time and date (object 50)
Time delay fine (object 52)
Class 0, 1, 2, and 3 data (object 60)
File transfer (object 70)
Internal indications (object 80)
Maximum data link frame size (octets):
Transmitted — 292
Received — 292
Maximum application fragment size (octets):
Transmitted — Configurable up to 2048
Received — 2048
Maximum data link re-tries — None
Maximum application layer re-tries — None
Requires data link layer confirmation — Never
Requires application layer confirmation — When reporting event data, when sending
multi-fragment responses
Timeouts while waiting for:
Data link confirm — None
Complete application fragment — None
Application confirm — Fixed at 10 seconds
Complete application response — None
Others:
Transmission delay — No intentional delay
Need time interval — Configurable (default is 24 hours)
Select/operate arm timeout — 10 seconds
Binary input change scanning period — 16 times per power system cycle
Analog input change scanning period — 500 ms
Counter change scanning period — 500 ms
Frozen counter event scanning period — 500 ms
Unsolicited response notification delay —100 ms
Unsolicited response retry delay — Configurable from 0 to 60 seconds
Sends/executes control operations:
Write binary outputs — Never
Select/operate — Always
Direct operate — Always
Direct operate – no acknowledge — Always
Count > 1 — Never
Pulse on — Sometimes
Pulse off — Sometimes
Latch on — Sometimes
Latch off — Sometimes
Queue — Never
Clear queue — Never
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE