MODBUS SETTINGS

Modbus settings

Modbus protocol

Modbus user map

8
This section outlines configuration settings from the instruction manual.
The Modbus server can simultaneously support one client over serial RS485 and four
clients over Ethernet. The server is capable of reporting any indication or measurement
and operating any output present in the device. A user-configurable input and output map
also is implemented.
Plus
The D90
operates as a Modbus slave device only.
In the EnerVista software, select the Settings > Communications > Modbus > Protocol
menu to open the Modbus protocol configuration window.
Figure 1: Modbus protocol configuration settings
The following settings are available.
Modbus Slave Address
Range: 1 to 254 in steps of 1
Default: 254
This setting specifies the Modbus slave address for the D90
unique address from 1 to 254. Address 0 and addresses from 248 and up are reserved by
the Modbus protocol specification, and so their use here is not recommended. Address 0
is the broadcast address to which all Modbus slave devices listen. Addresses do not have
to be sequential, but no two devices can have the same address or conflicts resulting in
errors occur. Generally, starting at 1, set each device added to the link to the next higher
address.
Modbus TCP Port Number
Range: 1 to 65535 in steps of 1
Default: 502
Modbus over TCP/IP can also be used on any of the Ethernet ports. This setting specifies
the Modbus TCP port number for Ethernet communications. Power to the D90
be cycled for changes to this setting to take effect.
Do not set more than one protocol to the same TCP/UDP port number, as this results in
unreliable operation of those protocols.
The Modbus user map provides read-only access for up to 256 registers. To obtain a
memory map value, enter the address in the Parameter field (this value must be converted
from hexadecimal to decimal format). The corresponding value (if programmed) displays in
the Value field. A value of "0" in subsequent register Address lines automatically returns
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE