CHAPTER 2: MODBUS COMMUNICATION
Address
Description
Phasor Measurement Unit One-Shot Command (Read/Write Setting)
E4BA
PMU One-Shot Function
E4BB
PMU One-Shot Sequence Number
E4BC
PMU One-Shot Time
Phasor Measurement Unit Trigger (Read/Write Setting)
E4BE
PMU Power Trigger Function
E4BF
PMU Power Trigger Active
E4C0
PMU Power Trigger Reactive
E4C1
PMU Power Trigger Apparent
E4C2
PMU Power Trigger Pkp Time
E4C3
PMU Power Trigger Dpo Time
E4C4
PMU Power Trigger Block
E4C8
PMU Power Trigger Events
Phasor Measurement Unit Recorder Configuration Counter (Read/Write Command)
E4C9
PMU Recorder Clear Configuration Counter
Phasor Measurement Unit Recording (Read/Write Setting)
E4CA
PMU Recording Rate
E4CC
PMU No of Time Records
E4CD
PMU Trigger Mode
E4CE
PMU Timed Trigger Position
E4D0
PMU Rec PHS-x (14 items)
E4DE
PMU Rec PHS-x Name (14 items)
E54E
PMU Rec A-CH-x (8 items)
E55E
PMU Rec D-CH-x Name (8 items)
E59E
PMU Rec D-CH-x (16 items)
E5AE
PMU Rec D-CH-x Name (16 items)
Phasor Measurement Unit Recording (Read/Write Command)
E62E
PMU Recording Clear Command
E62F
PMU Recording Force Trigger
Phasor Measurement Unit Recording (Read Only Actual Values)
E630
PMU Available Records
E631
PMU Second per Record
E633
PMU Last Cleared Date
E635
PMU Newest Record
Phasor Measurement Unit Records (Read Only Actual Values)
E636
PMU Recording Number of Triggers
Phasor Measurement Unit Test Values (Read/Write Setting)
E636
PMU Test Function
E637
PMU Phase A Voltage Test Magnitude
E639
PMU Page A Voltage Test Angle
E63A
PMU Phase B Voltage Test Magnitude
E63C
PMU Phase B Voltage Test Angle
E63D
PMU Phase C Voltage Test Magnitude
E63F
PMU Phase C Voltage Test Angle
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Units
0 to 1
---
0 to 59
---
0 to 235959
---
0 to 1
---
0.25 to 3
pu
0.25 to 3
pu
0.25 to 3
pu
0 to 600
s
0 to 600
s
0 to 65535
---
0 to 1
--
0 to 1
---
0 to 10
---
1 to 128
---
0 to 1
---
1 to 50
%
0 to 14
---
---
---
0 to 4294967295
---
---
---
0 to 65535
---
---
---
0 to 1
---
0 to 1
---
0 to 65535
---
0 to 429496729.5
---
0 to 400000000
---
0 to 65535
---
0 to 65535
---
0 to 1
---
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
MODBUS MEMORY MAP
Step
Format
Default
1
F102
0 (Disabled)
1
F001
0
1
F050
0
1
F102
0 (Disabled)
0.001
F001
1250
0.001
F001
1250
0.001
F001
1250
0.01
F001
10
0.01
F001
100
1
F300
0
1
F102
0 (Disabled)
1
F126
0 (No)
1
F544
3 (10/sec)
1
F001
3
1
F542
0 (Automatic
Overwrite)
1
F001
10
1
F543
0 (Off)
---
F203
"GE-UR+PMU-
PHS x"
1
F600
0
---
F203
"AnalogChan
nel x"
1
F300
0
---
F203
"Dig Channel
x"
1
F126
0 (No)
1
F126
0 (No)
1
F001
0
0.1
F003
0
1
F050
0
1
F001
0
1
F001
0
1
F102
0 (Disabled)
0.01
F003
50000
0.05
F002
0
0.01
F003
50000
0.05
F002
-12000
0.01
F003
50000
0.05
F002
12000