GE D90 Plus Communications Manual page 89

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Address
Description
587C
...Repeated for FlexLogic Timer 32
Phase Time Overcurrent (TOC) (Read/Write Grouped Setting) (6 Modules)
5900
Phase Time Overcurrent 1 Function
5901
Phase Time Overcurrent 1 Signal Source
5902
Phase Time Overcurrent 1 Input
5903
Phase Time Overcurrent 1 Pickup
5904
Phase Time Overcurrent 1 Curve
5905
Phase Time Overcurrent 1 Multiplier
5906
Phase Time Overcurrent 1 Reset
5907
Phase Time Overcurrent 1 Voltage Restraint
5908
Phase TOC 1 Block For Each Phase (3 items)
590C
Phase Time Overcurrent 1 Events
590D
Reserved (3 items)
5910
...Repeated for Phase Time Overcurrent 2
5920
...Repeated for Phase Time Overcurrent 3
5930
...Repeated for Phase Time Overcurrent 4
5940
...Repeated for Phase Time Overcurrent 5
5950
...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (IOC) (Read/Write Grouped Setting) (12 Modules)
5A00
Phase Instantaneous Overcurrent 1 Function
5A01
Phase Instantaneous Overcurrent 1 Signal Source
5A02
Phase Instantaneous Overcurrent 1 Pickup
5A03
Phase Instantaneous Overcurrent 1 Delay
5A04
Phase Instantaneous Overcurrent 1 Reset Delay
5A05
Phase IOC1 Block For Each Phase (3 items)
5A09
Phase Instantaneous Overcurrent 1 Events
5A0A
Phase Instantaneous Overcurrent 1 Reserved (6
items)
5A10
...Repeated for Phase Instantaneous Overcurrent 2
5A20
...Repeated for Phase Instantaneous Overcurrent 3
5A30
...Repeated for Phase Instantaneous Overcurrent 4
5A40
...Repeated for Phase Instantaneous Overcurrent 5
5A50
...Repeated for Phase Instantaneous Overcurrent 6
5A60
...Repeated for Phase Instantaneous Overcurrent 7
5A70
...Repeated for Phase Instantaneous Overcurrent 8
5A80
...Repeated for Phase Instantaneous Overcurrent 9
5A90
...Repeated for Phase Instantaneous Overcurrent 10
5AA0
...Repeated for Phase Instantaneous Overcurrent 11
5AB0
...Repeated for Phase Instantaneous Overcurrent 12
Neutral Time Overcurrent (TOC) (Read/Write Grouped Setting) (6 Modules)
5B00
Neutral Time Overcurrent 1 Function
5B01
Neutral Time Overcurrent 1 Signal Source
5B02
Neutral Time Overcurrent 1 Input
5B03
Neutral Time Overcurrent 1 Pickup
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Units
0 to 1
---
0 to 5
---
0 to 1
---
0 to 30
pu
0 to 16
---
0 to 600
---
0 to 1
---
0 to 1
---
0 to 65535
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 5
---
0 to 30
pu
0 to 600
s
0 to 600
s
0 to 65535
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 5
---
0 to 1
---
0 to 30
pu
MODBUS MEMORY MAP
Step
Format
Default
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
1
F122
0 (Phasor)
0.001
F001
1000
1
F103
0 (IEEE Mod
Inv)
0.01
F001
100
1
F104
0
(Instantaneou
s)
1
F102
0 (Disabled)
1
F300
0
1
F102
0 (Disabled)
1
F001
0
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
0.001
F001
1000
0.01
F001
0
0.01
F001
0
1
F300
0
1
F102
0 (Disabled)
1
F001
0
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
1
F122
0 (Phasor)
0.001
F001
1000
85