Settings in TROVIS-VIEW software

15.5 Initializing the positioner

Initializing the positioner is only possible in TROVIS-VIEW when the positioner has been at-
tached properly to the control valve and has been connected (see sections 4 and 5). The
positioner must be connected to the computer over the serial interface adapter.
NOTICE
During the initialization, the control valve moves through its entire travel/angle of rotation
range. Therefore, do not start initialization while a process is running, but only during
start-up, when all shut-off valves are closed.
Initialization using the Start Up Wizard
1. Start the Start Up Wizard by clicking the
2. Follow the on-screen prompts.
Manual initialization
1. Set the parameters in the Positioner folder (> Start-up ).
2. Enter the required initialization mode: Maximum range (MAX), nominal range (NOM),
manually selected range (MAN), substitute calibration (SUB) in the Positioner folder
( > Start-up-> Initialization ).
108
EB 8384-2 EN
button.