Samson Series 3730 Mounting And Operating Instructions page 87

Electropneumatic
Table of Contents

Advertisement

Parameter – Readings,
Code
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
49*
Partial stroke test (PST)/Full stroke test (FST) · Application type
A
Partial stroke test (PST)
A0 Start Partial Stroke Test
[No] · YES · ESC
A1 Time until the next auto-
matic PST test takes
place
A2 Desired PST testing
mode
Auto · [Man] · ESC
A3 Auto test time
A4 Status classification
PST status
[C] · OK · CR · b · S
ESC
A5 Min. recommended scan
time
A6 – Unassigned
A7 y-monitoring reference
value
Operating mode and PST testing mode must be set to MAN.
Display only
Remaining time [d_h] until the next partial stroke test is per-
formed. Only applies to PST Auto mode.
Activates (PST Auto) or deactivates (PST Man) the scheduled au-
tomatic partial stroke test.
Time [h] between for partial stroke tests (PST)
C
Maintenance required
OK
No message
CR
Maintenance demanded
b
Maintenance alarm
S
Out of specification
Display only
Scan time [s] required to plot the complete step response test in a
graph.
Display only
The valve moves to the valve position Step start (Code 49 - d2)
and Step end (Code 49 - d3) with certain control pulses. The dif-
ference between these control pulses creates the delta y value
[1/s].
The y-monitoring reference value applies to the adjusted step
values (Code 49 - d2 and Code 49 - d3) and for the selected
ramp times (Code 49 - d5 and Code 49 - d6). The y-monitoring
reference value must be determined again if any of the above
mentioned values change.
Description
Code list
87
EB 8384-2 EN