Data errors
Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
Control parameter
68
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
Poti parameter
69
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
Calibration parameter
70
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
General parameters
71
Status classification [Maintenance required]
Recommended action Confirm error.
Internal device error 1
73
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
Info parameter
75
Status classification [Maintenance required]
Recommended action Confirm error.
When error message exist, they are displayed here.
Control parameter error
Parameter error of the digital potentiometer.
Error in the production calibration data. Subsequently, the device
runs on default values.
Parameter errors that are not critical for the control.
Check and, if necessary, reset required parameters.
Internal device error
Internal positioner error
Check and, if necessary, reset required parameters.
Code list
97
EB 8384-2 EN