Code list
Parameter – Readings,
Code
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
36*
Reset
[No]
Std · diAG
ESC
Position transmitter
37
No · YES
38*
Inductive alarm
[No], YES, ESC
39
System deviation e info
–99.9 to 999.9 %
40
Transit time Open info
0 to 240 s [0]
41
Transit time Closed info
0 to 240 s [0]
Auto-w/manual-w info
42
0.0 to 100.0 % of the span
4 to 20 mA
Firmware info
43
Xxxx
44
y info
[0] to 100 %
0 P, MAX, – – –
84
EB 8384-2 EN
Std:
Resets all parameters to default (factory setting) as well
as the diagnosis data. After a reset, the positioner must
be re-initialized.
diAG: Resets diagnosis data only. Plotted reference graphs and
logs remain unaffected. The positioner does not need to
be re-initialized.
Display only,
indicates whether the position transmitter option is installed.
Indicates whether the inductive limit switch option is installed or
not.
Display only,
indicates the deviation from the target position (e = w – x).
Display only,
minimum opening time determined during initialization.
Display only,
minimum closing time determined during initialization.
Display only,
Supplied automatic reference variable according to 4 to 20 mA
Display only,
indicates the positioner type and current firmware version in
alternating sequence.
Display only.
Indicates the control signal y in % based on the travel range de-
termined on initialization
MAX:
The positioner builds up its maximum output pressure,
see description in Code 14 and 15.
0 P:
The positioner vents completely, see description in Code
14 and 15.
– – –:
The positioner is not initialized.