Parameter – Readings,
Code
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
49*
E
Cancelation conditions of the partial stroke test (PST)
E0 Activation x control
[No] · YES
E1 x control value
–10.0 to 110.0 % of
total trave, [0.0 %]
E2 – Unassigned
E3 – Unassigned
E4 – Unassigned
E5 Activation tolerance
band control
[No] · YES
E6 PST Tolerance band
0.1 to 100.0 %,
[5.0 %]
E7 Max. test duration
30 to 25000 s, [30 s]
F
Partial stroke test (PST) information · Read only
F0 No test available
F1 Test OK
F2 x cancelation
F3 y cancelation
F4 Tolerance band
exceeded
F5 Max. test time exceeded The test was not completed within the maximum test time and
F6 Test man. canceled
Activates/deactivates x control.
The test is automatically canceled as soon as the valve position
falls below this value.
Activates/deactivate tolerance band control.
The test is automatically canceled as soon as the Step end (Code
49 - d3) exceeds this value.
Maximum time within which a test can be completed before the
test is canceled automatically.
No test exists or the test has been canceled manually.
The test was canceled by the x cancelation function.
The test was canceled by the y cancelation function.
The test was canceled. The x-values exceeded the tolerance
band.
was automatically canceled.
The test has been manually canceled by the user.
Description
Code list
89
EB 8384-2 EN