Samson Series 3730 Mounting And Operating Instructions page 96

Electropneumatic
Table of Contents

Advertisement

Code list
Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
Hardware
65
Status classification [Maintenance alarm]
Recommended action Confirm error and return to the automatic operating mode, or
Data memory
66
Status classification Maintenance alarm (cannot be classified)
Recommended action Return the positioner to SAMSON AG for repair.
67
Test calculation
Status classification [Maintenance alarm]
Recommended action Confirm error. If this is not possible, return the positioner to
96
EB 8384-2 EN
When error messages exist, they are displayed here.
A hardware error has occurred, the positioner changes to the
fail-safe position (SAFE) .
perform a reset and re-initialize the device. If this is not success-
ful, return device to SAMSON AG for repair.
The writing of data to the data memory does not work anymore,
e.g. when the written data deviate from the read data.
Valve moves to the fail-safe position.
The hardware controller is monitored by means of a test
calculation.
SAMSON AG for repair.