Samson Series 3730 Mounting And Operating Instructions page 58

Electropneumatic
Table of Contents

Advertisement

Start-up – Settings
(Code 8 ) and travel/angle range end
(Code 9 ).
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
® Code 3 , display: No
Turn
Press
, Code 3 blinks
® YES
Turn
Press
, display
Enter the pin position:
mm
® Code 4
Turn
, Code 4 blinks
Press
Turn
® Pin position on lever (see rele-
vant section on attachment)
Press
. The reading of the nominal range
appears in mm/°.
58
EB 8384-2 EN
Default No
Pin position
Default No
Select the initialization mode:
® Code 6
Turn
, Code 6 blinks
Press
® MAN
Turn
to confirm the MAN as the initial-
Press
ization mode.
Enter OPEN position:
® Code 0
Turn
, Code 0 blinks
Press
Turn
® MAN
Press
.
® Code 1
Turn
, Code 1 blinks
Press
Turn
until the valve reaches its OPEN po-
sition.
Press
to confirm the OPEN position.
Start initialization:
4
Press INIT key to start initialization!
Initialization mode
Default MAX
Manual reference variable
(the current angle of rota-
tion is displayed)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730-23730 series3730-2 series

Table of Contents