Samson Series 3730 Mounting And Operating Instructions page 91

Electropneumatic
Table of Contents

Advertisement

Parameter – Readings,
Code
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
49*
h6 – Unassigned
h7 Limit value time analysis
0.6 to 30.0 s, [0.6 s]
h8 Limit value travel
analysis
0.1 to 100.0 % valve
position, [0.3 %]
h9 Status classification
Close/open
[C] · OK · CR · b · S
ESC
Note: The error codes listed in following appear in the display corresponding to their status
classification set over the condensed state (Maintenance required/Maintenance demanded:
, Out of specification:
to the error code as the status classification, the error is not included in the condensed state.
A status classification is assigned to every error code in the default setting. The status classifi-
cation of error codes can also be changed as required using an operating software (e.g.
TROVIS-VIEW). Refer to section 15.6.
Time limit for the difference between the reference value and the
latest recorded value. It determines at which difference value an
alarm is to be generated.
Travel limit for the difference between the reference value and
the latest recorded value. It determines at which difference value
an alarm is to be generated.
C
Maintenance required
OK No message
CR Maintenance demanded
b
Maintenance alarm
S
Out of specification
blinking, Maintenance alarm:
Description
). If "No message" is assigned
Code list
91
EB 8384-2 EN