Samson Series 3730 Mounting And Operating Instructions page 6

Electropneumatic
Table of Contents

Advertisement

Modifications of positioner firmware
Modifications of positioner firmware in comparison to previous versions
Previous
New
1.00
1.10
The serial interface and serial interface adapter allow the positioner to be operated
and configured using TROVIS-VIEW software
The following additional status messages were implemented:
Code 76 - No emergency mode
Code 77 - Program loading error
Displays number of zero calibrations performed since the last initialization.
For initialization of "AIR TO CLOSE" actuators, the direction of action (Code 7) is auto-
matically set to increasing/decreasing.
Code 3, the activation period of the enabled configuration function was
extended to 120 s.
1.10
1.20
Electronics changed, no new functions added.
1.20
1.30
New EXPERTplus diagnostics functions (Code 48) added
Positioner in EXPERTplus version with extended diagnostics features.
A running initialization can be canceled by pressing the rotary pushbutton.
The position transmitter (Code 37) and solenoid valve (Code 45) options are automati-
cally recognized.
1.30
1.40
All EXPERTplus functions can be used in this firmware version and higher.
The fault alarm contact is triggered by the condensed state of the positioner. It is al-
ways active when condensed state = "Maintenance alarm".
If Code 32 is set to Yes : Also active with "Function check" condensed state
If Code 33 is set to Yes : Also active with "Maintenance required/Maintenance de-
manded" condensed state
The "Function check" condensed state is additionally set for Test A1, A2, fault alarm
output and position transmitter.
The min./max. values of the temperature monitoring can be reset.
1.40
1.41
Internal modifications
1.41
1.42
Internal modifications
6
EB 8384-2 EN