Samson Series 3730 Mounting And Operating Instructions page 83

Electropneumatic
Table of Contents

Advertisement

Parameter – Readings,
Code
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
30*
Fault alarm ix
[No]
HI LO
ESC
Position transmitter test
31*
–10.0 to 110.0 [default
value is last indicated value
of the position transmitter]
% of the operating range
ESC
3)
Analog position transmitter: Code 29/30/31 can only be selected if the position transmitter (optional) is installed.
32*
Fault alarm with "Function
check" condensed state
[YES] · No
ESC
33*
Fault alarm with "Mainte-
nance required" condensed
state
[YES] · No
ESC
Closing direction
34*
CL [CCL]
ESC
35*
Blocking position
[0] mm/° /%
ESC
3)
Used to select whether faults causing the fault alarm contact to
switch should also be signaled by the position transmitter output
and how they should be signaled
HI ix = 21.6 ±0.1mA or LO ix = 2.4 ±0.1mA
3)
Testing the position transmitter. Values can be entered in relation
to the operating range.
The current actual value is used in initialized positioners locally
as the start value (bumpless changeover to the test mode). On
testing over software, the entered simulation value is issued as
the position feedback signal for 30 seconds.
YES: Fault alarm also with "Function check" condensed state
No: "Function check" condensed state does not cause a fault
alarm to be issued
Note: Regardless of the condensed state, the fault alarm output
always switches when error codes 57, 58, 60, 62 and 64 to 70,
76 are issued.
YES: Fault alarm only with "Maintenance alarm" condensed state
and with "Maintenance required" condensed state
No: Fault alarm only with "Maintenance alarm" condensed state
Note: Regardless of the condensed state, the fault alarm output
always switches when error codes 57, 58, 60, 62 and 64 to 70,
76 are issued.
CL: Clockwise, CCL: Counterclockwise
Turning direction in which the valve is moved to the CLOSED po-
sition (view onto the rotary switch motion when the positioner
cover is open).
Note: Needs only be entered in initialization mode SUb
(Code 6).
Entering the blocking position.
Distance up to the CLOSED position.
Note: Only necessary in initialization mode SUb.
Description
Code list
83
EB 8384-2 EN