Grounding The Switch - HP FlexFabric 12500E Installation Manual

Routing switch
Table of Contents

Advertisement

Figure 22 Installing L-shaped brackets
(1) Anchor bolt

Grounding the switch

WARNING!
For the safety of operators and equipment, securely ground the switch. Make sure the resistance reading
between the switch chassis and the ground is less than 1 ohm.
Most racks are equipped with a grounding strip. You can connect the yellow-green grounding cable of
the switch to the grounding strip.
CAUTION:
Connect the grounding cable to the earthing system in the equipment room. Do not connect it to a fire main
or lightning rod.
Use the supplied grounding cable (CAT 6 cable with dual-hole ring terminals).
To connect the grounding cable:
1.
Remove the two grounding screws from the switch chassis.
2.
Use the grounding screws to attach one end of the grounding cable to the chassis.
3.
Connect the other end of the grounding cable to the grounding strip of the rack in the same way.
(2) L-shaped bracket
27

Advertisement

Table of Contents
loading

Table of Contents