HP FlexFabric 12500E Installation Manual page 129

Routing switch
Table of Contents

Advertisement

Content
ODF-MN-B-C-R/T
Figure 89 Example of a label on an optical fiber between two devices
A01-01-05-05-R—The local end of the optical fiber is connected to Optical Receiving Interface 05
on Slot 5, Chassis 01 in the rack on Row A, Column 01 in the equipment room.
G01-01-01-01-T—The peer end of the optical fiber is connected to Optical Transmitting Interface 01
on Slot 01, Chassis 01 in the rack on Row G, Column 01 in the equipment room
Figure 90 Example of a label on an optical fiber between the device and the ODF
ODF-G01-01-01-R—The local end of the optical fiber is connected to the optical receiving terminal
on Row 01, Column 01 of the ODF in Row G Column 01 in the equipment room.
A01-01-05-05-R—The peer end of the optical fiber is connected to Optical Receiving Interface 5 on
Slot 05, Chassis 01 in the cabinet on Row A, Column 01 in the equipment room.
Meaning
D—Fiber port number
R—Optical receiving interface
T—Optical transmitting interface
MN—Row number and column
number of ODF
B—Row number of the terminal
device
C—Column number of the terminal
device
R—Optical receiving interface
T—Optical transmitting interface
123
Example
Numbered in top-down and left-right order with
two digits, for example, 05.
N/A
M—Row number of the rack in the equipment
room, in the range of A to Z.
N—Column number of the rack in the
equipment room, in the range of 01 to 99.
For example, G01 is the ODF of Row G and
Column 01.
In the range of 01 to 99, for example, 01-01.
N/A