Parameters Of The Pm-E F Pp Dc24V Profisafe; Diagnostic Functions Of The Pm-E F Pp Dc24V Profisafe - Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.3 PM-E F pp DC24V PROFIsafe power module
7.3.4

Parameters of the PM-E F pp DC24V PROFIsafe

STEP 7
Parameters in
The table below lists the parameters that can be set for the PM-E F pp DC24V PROFIsafe.
Table 7- 8
Parameter
F-Parameters:
F_destination_address
F monitoring time
See also
Configuration and Parameter Assignment (Page 26)
7.3.5

Diagnostic functions of the PM-E F pp DC24V PROFIsafe

Behavior in Case of Supply Voltage Failure
The failure of the PM-E F pp DC24V PROFIsafe power supply is always indicated by the
PWR LED on the module (light off). This information is also provided in the module
(diagnostic entry). The relay output of the module is passivated.
In the case of a voltage dip in the external auxiliary voltage, the SF LED lights up, the
module is passivated.
With the subsequent supply recovery (level must remain above the specified value for at
least 1 minute (refer to the technical specifications: voltages, currents, electrical potentials))
the SF LED goes out again, the module remains passivated. The SF LED flashes if there are
no other errors, until the error is acknowledged.
90
Parameters of the PM-E F pp DC24V PROFIsafe
Range
1 to 1022
10 to 10000 ms
Default
is assigned
STEP 7
by
150 ms
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Type of
Effective
Parameter
Range
Static
Module
Static
Module