Magnetic capacitance with inductive loads
Note
Note that an inductive load connected to the DO channels can induce voltages in the case of
electromagnetic interference of a strong magnetic field. This can cause a short-circuit error
message.
Remedy:
• Spatially disconnect the inductive loads or shield against the magnetic field.
• Set the parameters for the readback time to 50 ms or higher.
7.7.2

Terminal assignment of the EM 4 F-DO DC24V/2A PROFIsafe

Front View
Figure 7-48
The SF LED and the status displays of the inputs/outputs are not designed for safety-
related functions and may therefore not be evaluated for safety-related activities.
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Front view EM 4 F-DO DC24V/2A PROFIsafe
WARNING
7.7 4 F-DO DC24V/2A PROFIsafe digital electronic module
Fail-Safe Modules
165