Technical Specifications For Pm-E F Pm 24 Vdc Profisafe - Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.2 PM-E F pm DC24V PROFIsafe Power Module
Diagnostic
Message
Communication
error
Safety-related
shutdown
Generally Applicable Information on Diagnostics
For information on diagnostics that pertains to all fail-safe modules (e.g. for reading out
diagnostic functions, passivating channels), refer to the
manual.
See also
Reactions to Faults (Page 41)
7.2.6

Technical Specifications for PM-E F pm 24 VDC PROFIsafe

Overview
Dimensions and Weight
Dimensions W x H x D (mm)
Weight
Data for Specific Module
Number of outputs
Assigned address area
Length of cable*
78
Fault
Detection
Always
Always
Semiconductor outputs (P/M switching)
Relay outputs (P/M switching)
In the I/O area for inputs
In the I/O area for outputs
Unshielded
Possible Causes
Error in communication
between F-CPU and
module, e.g. due to
defective PROFIBUS
connection or higher
than permissible EMI
PROFIsafe monitoring
time set too low
Configuration of the F-
module does not match
safety program
Switching frequency
exceeded
Technical Specifications
30 x 81 x 52
Approx. 88 g
2
1
5 bytes
5 bytes
200 m, maximum
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Corrective Measures
Check the PROFIBUS/PROFINET
connection
Eliminate the interference
Set a greater value for the "F monitoring
time" parameter for the module in
HW Config
Generate safety program again; then load
configuration and safety program into F-
CPU again
Reduce the switching frequency or use a
semiconductor output
"Diagnostics"
chapter in this

Hide quick links: