Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual page 16

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Product Overview
1.3 Using ET 200S Fail-Safe Modules
Availability of Fail-Safe Electronic Modules
The following fail-safe electronic modules are available for ET 200S:
● Power module PM-E F pm DC24V PROFIsafe; switching to P/M potential, with 2
● Power module PM-E F pp DC24V PROFIsafe; switching to P/P potential
● Power module PM-D F DC24V PROFIsafe; switching to P/P potential
● Digital electronic module 4/8 F-DI DC24V PROFIsafe
● Digital electronic module 4 F-DI/3 F-DO DC24V PROFIsafe
● Digital electronic module 4 F-DO DC24V/2A PROFIsafe; switching to P/M potential
● Digital electronic module 1 F-RO DC24V/AC24..230V/5A
The PM-D F DC24V PROFIsafe is used for selective shutdowns of fail-safe motor starters
via six fail-safe shutdown groups.
A range of terminal modules is available for fail-safe power and electronic modules. You will
find a detailed list in this manual.
Using Interface Modules in ET 200S with Fail-Safe Modules
Depending on the F system, select the interface module for ET 200S as follows:
Table 1- 1
Interface module
IM 151-1 HIGH FEATURE
for PROFIBUS DP interface
IM 151-7 F-CPU for
PROFIBUS DP interface
IM 151-8 DP/PN F-CPU for
PROFINET IO interface
IM 151-3 PN HIGH
FEATURE for PROFINET IO
interface
The IM 151-1 HIGH FEATURE and the IM 151-3 PN HIGH FEATURE are described in the
respective manuals
PN/DP F-CPU are described in a separate product information.
Restrictions with EM 4 F-DI/3 F-DO DC24V PROFIsafe
The EM 4 F-DI/3 F-DO DC24V PROFIsafe only supports operation in distributed systems
with the following interface modules:
● 6ES7151-1BA01-0AB0 V2.0.0 or higher
● 6ES7151-3BA20-0AB0 V3.0.0 or higher
● 6ES7151-3BB21-0AB0 V3.0.0 or higher
The EM 4 F-DI/3 F-DO DC24V PROFIsafe can be used centrally with IM 151-7 F-CPU
6ES7151-7FA20-0AB0 V2.6 or higher or IM 151-8 F-CPU 6ES7151-8FB00-0AB0.
16
additional, fail-safe digital outputs
Using Interface Modules in ET 200S with Fail-Safe Modules
ET 200S Distributed I/O System
As of order number
6ES7151-1BA01-0AB0
6ES7151-7FA01-0AB0
6ES7151-8FB00-0AB0
6ES7151-3BA00-0AB0
6ES7151-3BA20-0AB0
6ES7151-3BB20-0AB0
Installation and Operating Manual, 08/2008, A5E00103686-07
Can be used in ET 200S
with optional package
S7 Distributed Safety
S7 F Systems
S7 Distributed Safety
S7 F Configuration Pack
S7 Distributed Safety
. The IM 151-7 F-CPU and IM 151-8
ET 200S Distributed I/O System - Fail-Safe Modules
As of version
V5.2
V5.2
V5.2
V5.5 SP5
V5.4

Hide quick links:

Advertisement

Table of Contents
loading