7.3

PM-E F pp DC24V PROFIsafe power module

7.3.1

Properties of the PM-E F pp DC24V PROFIsafe Power Module

Order Number
6ES7138-4CF42-0AB0
Properties
The PM-E F pp DC24V PROFIsafe power module possesses the following properties:
● Two relays for connecting voltage bus P2, 10 A output current
● Relay contacts must be fused externally
● Rated load voltage 24 VDC
● Suitable for solenoid valves, DC contactors and indicator lights
● Suitable for applications in which a grounded configuration is specified or where an
● Group fault display (SF; red LED)
● Status display for voltage bus P2 (green LED)
● Status display for load current power supply (PWR; green LED)
● Assignable diagnostics
● Achievable safety classes are listed in the table below
Table 7- 6
PM-E F pp DC24V PROFIsafe
Relay outputs P1
and P2
Supported Interface Modules
Refer to chapter "Using ET 200S Fail-Safe Modules (Page 14)" for the supported interface
modules.
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
ungrounded configuration cannot be guaranteed
Overview of available safety classes with PM-E F pp DC24V PROFIsafe
Without standard DO
modules
With standard DO modules
refer to the Internet
(http://support.automation.siemens.com/WW/vi
ew/en/12461959/133300)
7.3 PM-E F pp DC24V PROFIsafe power module
Maximum Attainable Safety
Class
Signal switches
SIL3/Category 4/PLe
daily or more often
Signal switches
SIL2/Category 3/PLd
less than once a
day
SIL2/Category 3/PLe
Fail-Safe Modules