Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual page 82

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.2 PM-E F pm DC24V PROFIsafe Power Module
Short-circuit protection of output
Time, Frequency
Internal processing times
Acknowledgment time in safety mode
Protection against Overvoltage
Protection of power supply L+ from surge in
accordance with IEC 61000-4-5 with external
protection elements only
Protection of outputs from surge in accordance
with IEC 61000-4-5 with external protection
elements only
Symmetrical (DO to M)
Asymmetrical (DO to PE, M to PE)
*: In order to achieve the specified cable length, you must route the P- and M-signal lines in a cable
or a sheathed cable.
**: Operating below the permissible supply voltage is only permissible for the repair time. See chapter
"Introduction (Page 61)."
***: For more information on the requirements for sensors and actuators, see
Modules"
82
With lamp load
Symmetrical (L+ to M)
Asymmetrical (L+ to PE, M to PE)
.
Technical Specifications
2 Hz, maximum
No, 10 A external circuit-breaker, "B"
characteristics required
"Response Times"
See
4 ms minimum/8 ms maximum
+ 1 kV; 1.2/50 μs
+2 kV; 1.2/50 μs
+ 1 kV; 1.2/50 μs
+ 1 kV; 1.2/50 μs
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
"Wiring and Fitting