Fail-Safe Modules
7.5 4/8 F-DI DC24V PROFIsafe Digital Electronic Module
Wiring Diagram for Application 2.3 – Connecting Two Single-Channel Sensors Nonequivalently via
Two Channels
The left-hand channels on the F-module (DI0 through DI3) supply the wanted signals. If no
faults are detected, these signals will be available in the I/O area for inputs on the F-CPU.
The sensors can also be connected to an external sensor supply.
Figure 7-28
To achieve SIL3/Category 3/PLe using this wiring, you must use a suitably qualified sensor.
Assignable Parameters for Application 2.3
Set the "sensor evaluation" to "1oo2 evaluation" at the corresponding input, and "2-channel
equivalent" at the "Type of sensor interconnection" parameter. Disable the "short-circuit test"
parameter.
For digital inputs connected to an external supply, set the "Sensor supply" parameter for the
corresponding digital input to "external".
124
Wiring diagram EM 4/8 F-DI DC24V - two 1-channel sensors connected via two
channels, internal sensor supply
WARNING
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07