Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual page 94

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.3 PM-E F pp DC24V PROFIsafe power module
Electrical isolation
Permissible potential difference between
Isolation in the series tested with
Isolation in the type test tested with
Current consumption
Power dissipation of the module
Status, Interrupts, Diagnostics
Status display
Diagnostic functions
Data for Selecting an Actuator for the Relay Output*
Switching capacity and service life of contacts
(voltage 24 VDC)
94
Between output and backplane bus
Between output and power supply
Between output/power supply and shield
shield and ET 200S bus connection
Shield and I/O (DOs, P1/P2 buses)
ET 200S bus connection and I/O (DOs, P1/P2
buses)
Shield and ET 200S bus connection
Shield and I/O (DOs, P1/P2 buses)
ET 200S bus connection and I/O (DOs, P1/P2
buses)
Shield and ET 200S bus connection
Shield and I/O (DOs, P1/P2 buses)
ET 200S bus connection and I/O (DOs, P1/P2
buses)
Surge voltage test between ET 200S bus
connection and I/O (DOs, P1/P2 buses)
From backplane bus
From load voltage L+ (without load)
Group fault display
Diagnostic information can be displayed
Mechanical endurance (without load)
For resistive load
Technical Specifications
Yes
No
Yes
75 VDC/60 VAC
75 VDC/60 VAC
250 VAC
500 VDC/1 min or 600 VDC/1 s
500 VDC/1 min or 600 VDC/1 s
1500 VAC/1 min or 2545 VDC/1 s
350 VAC/1 min
350 VAC/1 min
2830 VAC/1 min
6000 VDC/5 positive and 5 negative pulses
28 mA, maximum
100 mA, typical
4 W, typical
Green LED per channel
Green LED for the load voltage
Red LED (SF)
Possible
Current
0 A
Current
10 A
8 A
6 A
4 A
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Number of switching cycles (typ.)
10 million
Number of switching cycles (typ.)
0.23 million
0.3 million
0.38 million
0.5 million