Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual page 135

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Input current
Input delay *
Input characteristic
Connection of 2-wire proximity switch (BERO)
Time, Frequency
Internal processing times
Acknowledgment time in safety mode
Minimum sensor signal duration
Protection against Overvoltage
Protection of power supply L+ from surge in
accordance with IEC 61000-4-5 with external
protection elements only
Protection of inputs and outputs from surge in
accordance with IEC 61000-4-5 with external
protection elements only
*: With an input delay of 0.5 ms, shielded cables must be used for the digital inputs and the sensor
supply.
With 3 ms input delay, shielded cables must be used if there is a danger of overvoltage on the signal
lines (see section "Electromagnetic Compatibility") to prevent possible passivation of the fail-safe
digital inputs and the sensor power supply switching off. If unshielded signal lines are used, the safe
behavior of the process variables is ensured.
**: Operating below the permissible supply voltage is only permissible for the repair time. See chapter
"Introduction (Page 61)."
***: For more information on the requirements for sensors and actuators, see "Wiring and Fitting
Modules".
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
For "1" signal
For "0" after "1"
bei "1" nach "0"
Permissible quiescent current
Short-circuit test activated
With input delay of 0.5 ms:
With input delay of 3 ms:
With input delay of 15 ms:
Short-circuit test deactivated
Symmetrical (L+ to M)
Asymmetrical (L+ to PE, M to PE)
Symmetrical (Vs, DI to M)
Asymmetrical (Vs, DI to PE, M to PE)
7.5 4/8 F-DI DC24V PROFIsafe Digital Electronic Module
Technical Specifications
3.7 mA, typical
Assignable (for all inputs together)
Typically 0.5 ms
Typically 3 ms
Typically 15 ms
Typically 0.5 ms
Typically 3 ms
Typically 15 ms
In accordance with IEC 61131-2 Type 1
Not possible
0.6 mA, maximum
"Response Times"
See
Min. 4 ms / max. 7 ms
Min. 4 ms / max. 12 ms
Min. 4 ms / max. 9 ms
Min. 4 ms / max. 6 ms
"Minimum Duration of Sensor Signals to
See
Allow Correct Detection by the F-DI Module"
"Wiring and Fitting Modules"
table in
1 kV; 1.2/50 μs
+2 kV; 1.2/50 μs
+1 kV; 1.2/50 μs
+1 kV; 1.2/50 μs
Fail-Safe Modules
(0.3 ms to 0.7 ms)
(2.6 ms to 3.4 ms)
(13 ms to 17 ms)
(0.3 ms to 0.7 ms)
(2.6 ms to 3.4 ms)
(13 ms to 17 ms)
135