Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual page 104

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.4 PM-D F DC24V PROFIsafe Power Module
Isolation in the series tested with
Isolation in the type test tested with
Current consumption
Power dissipation of the module
Status, Interrupts, Diagnostics
Status display
Diagnostic functions
Time, Frequency
Internal processing times
Acknowledgment time in safety mode
Protection against Overvoltage
Protection of power supply L+ from surge in
accordance with IEC 61000-4-5 with external
protection elements only
*: Operating below the permissible supply voltage is only permissible for the repair time. See chapter
"Introduction (Page 61)."
104
Shield and ET 200S bus connection
Shield and I/O (SGs, U 1 bus)
ET 200S bus connection and I/O (SGs, U 1
bus)
Shield and ET 200S bus connection
Shield and I/O (SGs, U 1 bus)
ET 200S bus connection and I/O (SGs, U 1
bus)
Shield and ET 200S bus connection
Shield and I/O (SGs, U 1 bus)
ET 200S bus connection and I/O (SGs, U 1
bus)
Surge voltage test between ET 200S bus
connection and I/O (SGs, U1 bus)
From backplane bus
From load voltage L+ (without load)
Group fault display
Diagnostic information can be displayed
Symmetrical (L+ to M)
Asymmetrical (L+ to PE, M to PE)
Technical Specifications
75 VDC/60 VAC
75 VDC/60 VAC
250 VAC
500 VDC/1 min or 600 VDC/1 s
500 VDC/1 min or 600 VDC/1 s
1500 VAC/1 min or 2545 VDC/1 s
350 VAC/1 min
350 VAC/1 min
2830 VAC/1 min
6000 VDC/5 positive and 5 negative pulses
28 mA, maximum
100 mA, typical
4 W, typical
Green LED per SG
Green LED for electronic power supply
Green LED for the load voltage
Red LED (SF)
Possible
"Response Times"
See
4 ms minimum/8 ms maximum
+ 1 kV; 1.2/50 μs
+2 kV; 1.2/50 μs
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07