7.7 4 F-DO DC24V/2A PROFIsafe digital electronic module
Switching Grounded Loads
If the EM 4 F-DO DC24V/2A PROFIsafe switches loads that have a chassis-ground
connection (for example to improve EMC characteristics) and if chassis and ground are
connected at the power supply being used, a "short circuit" is detected.
From the perspective of the F-module, the M-switch is bridged by the chassis-ground
connection (refer to the diagram below as an example of an EM 4 F-DO DC24V/2A
PROFIsafe).
Remedy:
● Using the PM-E F pp DC24V PROFIsafe
● The value of the resistance between chassis and ground at the load end must be greater
Capacitive Crosstalk of Digital Input/Output Signals
Refer to
164
than 100 kΩ
Figure 7-47
Switching Grounded Loads (with resistance between chassis and ground)
"Properties of the power module PM-E F pm DC24V PROFIsafe"
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
.