Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual page 68

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.2 PM-E F pm DC24V PROFIsafe Power Module
The SF LED and the status displays of the inputs/outputs are not designed for safety-
related functions and may therefore not be evaluated for safety-related activities.
Terminal Assignment
The following figure and the following table show the terminal assignment of the PM-
E F pm DC 24V PROFIsafe for the supported terminal modules TM-P30S44-A0 or TM-
P30C44-A0.
Figure 7-4
Table 7- 2
Terminal
2
3
A
4
6
7
68
WARNING
Terminal assignment TM-P30S44-A0 or TM-P30C44-A0 for PM-E F pm DC 24V
PROFIsafe
Terminal assignment of the TM-P30S44-A0 or TM-P30C44-A0
Designation
24 VDC
24 VDC rated load voltage for:
Inserted power module
Corresponding potential group
DO 0 and DO 1
Voltage buses P1 and P2
M
Ground
AUX 1
Any terminal for PE or voltage bus up to the maximum rated load voltage of the
module
24 VDC
24 VDC rated load voltage for:
Inserted power module
Corresponding potential group
DO 0 and DO 1
Voltage buses P1 and P2
M
Ground
ET 200S Distributed I/O System - Fail-Safe Modules