Parameters Of The Pm-E F Pm Dc24V Profisafe - Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.2 PM-E F pm DC24V PROFIsafe Power Module
7.2.4

Parameters of the PM-E F pm DC24V PROFIsafe

STEP 7
Parameters in
The table below lists the parameters that can be set for the PM-E F pm DC24V PROFIsafe.
Table 7- 3
Parameter
F-Parameters:
F_destination_address 1 to 1022
F monitoring time
Module Parameters:
Behavior after channel
faults*
DO channel 0
Readback time
Diagnostics: Wire
break
DO channel 1
Readback time
Diagnostics: Wire
break
* This setting is relevant only with an installed
S7 F systems
Readback Time Parameter
Each output channel has its own selectable readback time. This time specifies the maximum
duration of the turn off test for the corresponding channel and therefore also the readback
time for turning off the channel.
The following readback times can be set: 1 ms, 5 ms, 10 ms, 50 ms, 100 ms, 200 ms and
400 ms.
You should set an adequately high readback time if the channel involved switches high
capacitive loads. If the readback time for a controlled capacitive load is set too low, the
output channel is passivated because the discharge of the capacitance does not take place
within the turn off test.
If the readback signals are incorrect, the "short circuit" fault only causes passivation of the
output channel after the readback time has elapsed.
74
Parameters of the PM-E F pm DC24V PROFIsafe
Range
10 to 10 000 ms
Passivate the entire
module/Passivate
the channel
Activated/deactivate
d
1 to 400 ms
Activated/deactivate
d
Activated/deactivate
d
1 to 400 ms
Activated/deactivate
d
optional packages.
Default
Type of Parameter
is assigned by
Static
STEP 7
150 ms
Static
Passivate the
Static
entire module
Activated
Static
1 ms
Static
Deactivated
Static
Activated
Static
1 ms
Static
Deactivated
Static
S7 distributed safety
V 5.4 or higher or generally with
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Effective
Range
Module
Module
Module
Channel
Channel
Channel
Channel
Channel
Channel