Total current of outputs
•
•
Electrical isolation
•
•
•
•
Permissible potential difference between
•
•
•
Isolation in the series tested with
•
•
•
Isolation in the type test tested with
•
•
•
•
Current consumption
•
•
Power dissipation of the module
Status, Interrupts, Diagnostics
Status display
Outputs
Diagnostic functions
•
•
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Horizontal installation
–
Up to 40 °C
–
Up to 55 °C
–
Up to 60 °C
Vertical installation
–
Up to 40 °C
Between channels and backplane bus
Between channels and power supply
Between channels
Between channels/power supply and shield
Shield and ET 200S bus connection
Shield and I/O (DOs, P1/P2 buses)
ET 200S bus connection and I/O (DOs, P1/P2
buses)
Shield and ET 200S bus connection
Shield and I/O (DOs, P1/P2 buses)
ET 200S bus connection and I/O (DOs, P1/P2
buses)
Shield and ET 200S bus connection
Shield against I/O (DOs, P1/P2 buses)
ET 200S bus connection against I/O (DOs,
P1/P2 buses)
Surge voltage test between ET 200S bus
connection and I/O (DOs, P1/P2 buses)
From backplane bus
From load voltage L+ (without load)
Group fault display
Diagnostic information can be displayed
7.7 4 F-DO DC24V/2A PROFIsafe digital electronic module
Technical Specifications
6 A
5 A
4 A
4 A
Yes
No
No
Yes
75 VDC/60 VAC
75 VDC/60 VAC
250 VAC
500 VDC/1 min or 600 VDC/1 s
500 VDC/1 min or 600 VDC/1 s
1500 VAC/1 min or 2545 VDC/1 s
350 VAC/1 min
350 VAC/1 min
2830 VAC/1 min
6000 VDC/5 positive and 5 negative pulses
28 mA, maximum
100 mA, typical
3.5 W, typical
Green LED per channel
Red LED (SF)
Possible