Ro Dc24V/Ac24; Properties Of The Em 1 F-Ro Dc24V/Ac24..230V/5A - Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Protection of inputs and outputs from surge in
accordance with IEC 61000-4-5 with external
protection elements only
*: In order to achieve the specified cable length, you must route the P and M-signal lines in a cable or
a sheathed cable.
**: Operating below the permissible supply voltage is only permissible for the repair time. See chapter
"Introduction (Page 61)."
***: For more information on the requirements for sensors and actuators see
Modules"
7.8
1 F-RO DC24V/AC24..230V/5A Digital Electronic Module
7.8.1

Properties of the EM 1 F-RO DC24V/AC24..230V/5A

Order Number
6ES7138-4FR00-0AA0
Properties
The 1 F-RO DC24V/AC24..230V/5A digital electronic module disposes of the following
properties:
● 1 relay output (2 2-channel contacts)
● Output current 5 A
● Rated load voltage 24 VDC and 24 VAC to 230 VAC
● Status display for output (green LED)
● safety class SIL3/Category 4/PLe can be achieved if the F-RO module is controlled by a
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
Symmetrical (L+ to M)
Asymmetrical (L+ to PE, M to PE)
Symmetrical (L+ to M)
Asymmetrical (L+ to PE, M to PE)
.
fail-safe output (for example, by EM 4F-DO DC24V/2A PROFIsafe)
7.8 1 F-RO DC24V/AC24..230V/5A Digital Electronic Module
Technical Specifications
+ 1 kV; 1.2/50 μs
+2 kV; 1.2/50 μs
+1 kV; 1.2/50 μs
+2 kV; 1.2/50 μs
Fail-Safe Modules
"Wiring and Fitting
177

Hide quick links: