Siemens PM-E F pm DC24V PROFIsafe Installation And Operating Manual page 102

Et 200s distributed i/o system - fail-safe modules
Table of Contents

Advertisement

Fail-Safe Modules
7.4 PM-D F DC24V PROFIsafe Power Module
Causes of Faults and Corrective Measures
The following table contains the possible causes of the faults described for the individual
diagnostic messages of the PM-D F DC24V PROFIsafe and remedies.
Table 7- 15
Diagnostics
Message
Short circuit
Overtemperatur
e
Internal error
Parameter
assignment
error
external
auxiliary supply
missing
Communication
error
Generally Applicable Information on Diagnostics
For information on diagnostics that pertains to all fail-safe modules (for reading out
diagnostic functions, passivating channels, for example), refer to
manual.
See also
Fault Diagnostics (Page 43)
102
Diagnostic messages of the PM-D F DC24V PROFIsafe, causes of errors and remedies
Fault
Possible Causes
Detection
Always
Short circuit in the
actuator
Cross circuit in the
actuator
Internal error
Always
Shutdown due to
violation of upper or
lower temperature limit
in the module case.
Always
Internal module fault
has occurred
Always
Inserted module does
not match
configuration. Incorrect
parameter assignment
PROFIsafe address set
incorrectly in the F-
module
Always
No supply voltage or
supply voltage is too
low.
Always
Error in communication
between F-CPU and
module due to
defective PROFIBUS
connection or higher
than permissible EMI,
for example
PROFIsafe monitoring
time set too low
Corrective Measures
Eliminate short-circuit/cross-circuit; once
the fault has been eliminated, the module
must be removed and inserted, or the
power switched OFF and ON
Replace module
Check load wiring, check ambient
temperature. Once the fault has been
eliminated, the module must be removed
and inserted, or the power switched off
and on.
Replace module
Correct the configuration (compare actual
and preset configuration), and check
communication paths. Correct the
parameter assignment.
Check whether the PROFIsafe address
on the module matches the configuration
HW Config
in
Check module for correct contact
Test PROFIBUS/PROFINET connection.
Correct faults
Set a greater value for the "F monitoring
time" parameter for the module in
HW Config
Diagnostics
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
chapter in this